Siemens SIMATIC ET 200AL IM 157-1 PN

CVE-2025-40944
HIGH 8.7

At a glance

Source
NVD
EPSS
EPSS 0.44 % · percentile 38 ()
State
PUBLISHED
Published
Updated
Assigner
siemens
NVD status
Deferred

Description

A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0 < V4.2.5), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state. This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.

Weaknesses (CWE)

  • CWE-400 — Uncontrolled Resource Consumption

References

Scores

VersionScoreVectorScored by
CVSS 3.1HIGH 7.5CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsiemens
CVSS 4.0HIGH 8.7CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:Nsiemens
CVSS 4.0HIGH 8.7CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:XNVD · productcert@siemens.com (Secondary)
CVSS 3.1HIGH 7.5CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:HNVD · productcert@siemens.com (Secondary)

European references

CERT-FR advisories

Affected products

ProductVersions
Siemens · SIMATIC ET 200AL IM 157-1 PNaffected 0 < *
Siemens · SIMATIC ET 200MP IM 155-5 PN HFaffected V4.2.0 < *
Siemens · SIMATIC ET 200SP IM 155-6 MF HFaffected 0 < *
Siemens · SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)affected 0 < V1.3
Siemens · SIMATIC ET 200SP IM 155-6 PN R1affected 0 < V6.0.1
Siemens · SIMATIC ET 200SP IM 155-6 PN/2 HFaffected V4.2.0 < V4.2.5
Siemens · SIMATIC ET 200SP IM 155-6 PN/3 HFaffected 0 < V4.2.2
Siemens · SIMATIC PN/MF Coupleraffected 0 < *
Siemens · SIMATIC PN/PN Coupleraffected 0 < V6.0.0
Siemens · SIPLUS ET 200MP IM 155-5 PN HFaffected V4.2.0 < *
Siemens · SIPLUS ET 200MP IM 155-5 PN HFaffected V4.2.0 < *
Siemens · SIPLUS ET 200MP IM 155-5 PN HF T1 RAILaffected V4.2.0 < *
Siemens · SIPLUS ET 200SP IM 155-6 PN HFaffected V4.2.0 < V4.2.5
Siemens · SIPLUS ET 200SP IM 155-6 PN HFaffected V4.2.0 < V4.2.5
Siemens · SIPLUS ET 200SP IM 155-6 PN HF T1 RAILaffected V4.2.0 < V4.2.5
Siemens · SIPLUS ET 200SP IM 155-6 PN HF TX RAILaffected V4.2.0 < V4.2.5
Siemens · SIPLUS NET PN/PN Coupleraffected 0 < V6.0.0

Sources

SourceLicence
CVE List (CVEProject cvelistV5)CVE Program Terms of Use
EPSS (FIRST.org)FIRST — attribution requested
ENISA EUVDENISA — reproduction authorised, source acknowledged
CERT-FR (ANSSI)Licence Ouverte / Etalab 2.0
NVD (NIST) via fkie-cad/nvd-json-data-feedsPublic domain — this product uses data from the NVD API but is not endorsed or certified by the NVD