Schneider Electric Modicon M340 CPU (part numbers BMXP34*)
En bref
- Source
- NVD
- EPSS
- EPSS 0.63 % · centile 50 ()
- État
- PUBLISHED
- Publiée
- Mise à jour
- Attribuée par
- schneider
- Statut NVD
- Modified
Rechercher sur…
Description
A CWE-200: Information Exposure vulnerability exists that could cause the exposure of sensitive information stored on the memory of the controller when communicating over the Modbus TCP protocol. Affected Products: Modicon M340 CPU (part numbers BMXP34*) (Versions prior to V3.30), Modicon M580 CPU (part numbers BMEP* and BMEH*) (Versions prior to SV3.20), Modicon MC80 (BMKC80) (Versions prior to V1.6), Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S) (All Versions), Modicon Momentum MDI (171CBU*) (Versions prior to V2.3), Legacy Modicon Quantum (All Versions)
Faiblesses (CWE)
- CWE-200 — Exposition d'informations sensibles à un acteur non autorisé
Références
Scores
| Version | Score | Vecteur | Évalué par |
|---|---|---|---|
| CVSS 3.1 | HIGH 7.5 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N | schneider |
| CVSS 3.1 | HIGH 7.5 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N | NVD · cybersecurity@se.com (Secondary) |
| CVSS 3.1 | HIGH 7.5 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N | NVD · nvd@nist.gov (Primary) |
Références européennes
- ENISA EUVD · EUVD-2021-9921
- GCVE · GCVE-0-2021-22786
Avis du CERT-FR
- CERTFR-2022-AVI-717 — Multiples vulnérabilités dans les produits Schneider · cert.ssi.gouv.fr
- CERTFR-2022-AVI-1093 — Multiples vulnérabilités dans les produits Schneider · cert.ssi.gouv.fr
Configurations affectées (CPE NVD)
cpe:2.3:o:schneider-electric:modicon_m340_bmxp341000_firmware:*:*:*:*:*:*:*:*< 3.40cpe:2.3:o:schneider-electric:modicon_m340_bmxp342000_firmware:*:*:*:*:*:*:*:*< 3.40cpe:2.3:o:schneider-electric:modicon_m340_bmxp342010_firmware:*:*:*:*:*:*:*:*< 3.40cpe:2.3:o:schneider-electric:modicon_m340_bmxp3420102_firmware:*:*:*:*:*:*:*:*< 3.40cpe:2.3:o:schneider-electric:modicon_m340_bmxp342020_firmware:*:*:*:*:*:*:*:*< 3.40cpe:2.3:o:schneider-electric:modicon_m340_bmxp342020h_firmware:*:*:*:*:*:*:*:*< 3.40cpe:2.3:o:schneider-electric:modicon_m340_bmxp342030_firmware:*:*:*:*:*:*:*:*< 3.40cpe:2.3:o:schneider-electric:modicon_m340_bmxp3420302_firmware:*:*:*:*:*:*:*:*< 3.40cpe:2.3:o:schneider-electric:modicon_m340_bmxp3420302h_firmware:*:*:*:*:*:*:*:*< 3.40cpe:2.3:o:schneider-electric:modicon_m340_bmxp342030h_firmware:*:*:*:*:*:*:*:*< 3.40cpe:2.3:o:schneider-electric:modicon_m580_bmeh582040_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmeh582040c_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmeh582040s_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmeh584040_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmeh584040c_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmeh584040s_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmeh586040_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmeh586040c_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmeh586040s_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmep581020_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmep581020h_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmep582020_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmep582020h_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmep582040_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmep582040h_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmep582040s_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmep583020_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmep583040_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmep584020_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmep584040_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmep584040s_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmep585040_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmep585040c_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmep586040_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_m580_bmep586040c_firmware:*:*:*:*:*:*:*:*≤ 3.20cpe:2.3:o:schneider-electric:modicon_momentum_171cbu78090_firmware:*:*:*:*:*:*:*:*< 2.4cpe:2.3:o:schneider-electric:modicon_momentum_171cbu98090_firmware:*:*:*:*:*:*:*:*< 2.4cpe:2.3:o:schneider-electric:modicon_momentum_171cbu98091_firmware:*:*:*:*:*:*:*:*< 2.4cpe:2.3:o:schneider-electric:modicon_mc80_bmkc8020301_firmware:*:*:*:*:*:*:*:*< 1.70cpe:2.3:o:schneider-electric:modicon_mc80_bmkc8020310_firmware:*:*:*:*:*:*:*:*< 1.70- +1 autres
Produits affectés
| Produit | Versions |
|---|---|
| Schneider Electric · Modicon M340 CPU (part numbers BMXP34*) | affected All < V3.30 |
| Schneider Electric · Modicon M580 CPU (part numbers BMEP* and BMEH*) | affected All < V3.20 |
| Schneider Electric · Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S) | affected All Versions |
| Schneider Electric · Modicon MC80 (BMKC80) | affected All < V1.6 |
| Schneider Electric · Modicon Momentum CPU (171CBU*) | affected All < V2.3 |
| Schneider Electric · Legacy Modicon Quantum | affected All Versions |
Sources
| Source | Licence |
|---|---|
| CVE List (CVEProject cvelistV5) | CVE Program Terms of Use |
| EPSS (FIRST.org) | FIRST — attribution requested |
| ENISA EUVD | ENISA — reproduction authorised, source acknowledged |
| CERT-FR (ANSSI) | Licence Ouverte / Etalab 2.0 |
| NVD (NIST) via fkie-cad/nvd-json-data-feeds | Public domain — this product uses data from the NVD API but is not endorsed or certified by the NVD |