Siemens AG SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules

CVE-2019-19279
HIGH 7.5

At a glance

Source
NVD
EPSS
EPSS 1.59 % · percentile 76 ()
State
PUBLISHED
Published
Updated
Assigner
siemens
NVD status
Modified

Description

A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules (All versions). Specially crafted packets sent to port 50000/UDP of the EN100 Ethernet communication modules could cause a Denial-of-Service of the affected device. A manual reboot is required to recover the service of the device. At the time of advisory publication no public exploitation of this security vulnerability was known to Siemens.

Weaknesses (CWE)

  • CWE-20 — Improper Input Validation

References

Scores

VersionScoreVectorScored by
CVSS 3.1HIGH 7.5CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:HNVD · nvd@nist.gov (Primary)
CVSS 2.0HIGH 7.8AV:N/AC:L/Au:N/C:N/I:N/A:CNVD · nvd@nist.gov (Primary)

European references

CERT-FR advisories

Affected configurations (NVD CPE)

Affected products

ProductVersions
Siemens AG · SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modulesaffected All versions

Sources

SourceLicence
CVE List (CVEProject cvelistV5)CVE Program Terms of Use
EPSS (FIRST.org)FIRST — attribution requested
ENISA EUVDENISA — reproduction authorised, source acknowledged
CERT-FR (ANSSI)Licence Ouverte / Etalab 2.0
NVD (NIST) via fkie-cad/nvd-json-data-feedsPublic domain — this product uses data from the NVD API but is not endorsed or certified by the NVD