Siemens LOGO! 8 BM (incl. SIPLUS variants)

CVE-2019-10920
HIGH 7.5

At a glance

Source
NVD
EPSS
EPSS 1.50 % · percentile 74 ()
State
PUBLISHED
Published
Updated
Assigner
siemens
NVD status
Modified

Description

A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). Project data stored on the device, which is accessible via port 10005/tcp, can be decrypted due to a hardcoded encryption key. The security vulnerability could be exploited by an unauthenticated attacker with network access to port 10005/tcp. No user interaction is required to exploit this security vulnerability. The vulnerability impacts confidentiality of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.

Weaknesses (CWE)

  • CWE-321 — Use of Hard-coded Cryptographic Key
  • CWE-798 — Use of Hard-coded Credentials

References

Scores

VersionScoreVectorScored by
CVSS 3.1HIGH 7.5CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:NNVD · nvd@nist.gov (Primary)
CVSS 2.0MEDIUM 5.0AV:N/AC:L/Au:N/C:P/I:N/A:NNVD · nvd@nist.gov (Primary)

European references

CERT-FR advisories

Affected configurations (NVD CPE)

Affected products

ProductVersions
Siemens · LOGO! 8 BM (incl. SIPLUS variants)affected All versions < V8.3

Sources

SourceLicence
CVE List (CVEProject cvelistV5)CVE Program Terms of Use
EPSS (FIRST.org)FIRST — attribution requested
ENISA EUVDENISA — reproduction authorised, source acknowledged
CERT-FR (ANSSI)Licence Ouverte / Etalab 2.0
NVD (NIST) via fkie-cad/nvd-json-data-feedsPublic domain — this product uses data from the NVD API but is not endorsed or certified by the NVD