Siemens LOGO! 8 BM (incl. SIPLUS variants)

CVE-2019-10919
CRITICAL 9.4

At a glance

Source
NVD
EPSS
EPSS 2.75 % · percentile 86 ()
State
PUBLISHED
Published
Updated
Assigner
siemens
NVD status
Modified

Description

A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). Attackers with access to port 10005/tcp could perform device reconfigurations and obtain project files from the devices. The system manual recommends to protect access to this port. The security vulnerability could be exploited by an unauthenticated attacker with network access to port 10005/tcp. No user interaction is required to exploit this security vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.

Weaknesses (CWE)

  • CWE-306 — Missing Authentication for Critical Functionality

References

Scores

VersionScoreVectorScored by
CVSS 3.1CRITICAL 9.4CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:LNVD · nvd@nist.gov (Primary)
CVSS 2.0HIGH 7.5AV:N/AC:L/Au:N/C:P/I:P/A:PNVD · nvd@nist.gov (Primary)

European references

CERT-FR advisories

Affected configurations (NVD CPE)

Affected products

ProductVersions
Siemens · LOGO! 8 BM (incl. SIPLUS variants)affected All versions < V8.3

Sources

SourceLicence
CVE List (CVEProject cvelistV5)CVE Program Terms of Use
EPSS (FIRST.org)FIRST — attribution requested
ENISA EUVDENISA — reproduction authorised, source acknowledged
CERT-FR (ANSSI)Licence Ouverte / Etalab 2.0
NVD (NIST) via fkie-cad/nvd-json-data-feedsPublic domain — this product uses data from the NVD API but is not endorsed or certified by the NVD