Siemens AG SIMATIC HMI Comfort Panels 4" - 22", SIMATIC HMI Comfort Outdoor Panels 7" & 15", SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F, SIMATIC WinCC Runtime Advanced, SIMATIC WinCC Runtime Professional, SIMATIC WinCC (TIA Portal), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel)

CVE-2018-13812
HIGH 7.5

At a glance

Source
NVD
EPSS
EPSS 3.57 % · percentile 89 ()
State
PUBLISHED
Published
Updated
Assigner
siemens
NVD status
Modified

Description

A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15 Update 4), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15 Update 4), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15 Update 4), SIMATIC WinCC Runtime Advanced (All versions < V15 Update 4), SIMATIC WinCC Runtime Professional (All versions < V15 Update 4), SIMATIC WinCC (TIA Portal) (All versions < V15 Update 4), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). A directory traversal vulnerability could allow to download arbitrary files from the device. The security vulnerability could be exploited by an attacker with network access to the integrated web server. No user interaction and no authentication is required to exploit the vulnerability. The vulnerability impacts the confidentiality of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.

Weaknesses (CWE)

  • CWE-22 — Improper Limitation of a Pathname to a Restricted Directory

References

Scores

VersionScoreVectorScored by
CVSS 3.0HIGH 7.5CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:NNVD · nvd@nist.gov (Primary)
CVSS 2.0MEDIUM 5.0AV:N/AC:L/Au:N/C:P/I:N/A:NNVD · nvd@nist.gov (Primary)

European references

CERT-FR advisories

Affected configurations (NVD CPE)

Affected products

ProductVersions
Siemens AG · SIMATIC HMI Comfort Panels 4" - 22", SIMATIC HMI Comfort Outdoor Panels 7" & 15", SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F, SIMATIC WinCC Runtime Advanced, SIMATIC WinCC Runtime Professional, SIMATIC WinCC (TIA Portal), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel)affected SIMATIC HMI Comfort Panels 4" - 22" : All versions < V15 Update 4 ; affected SIMATIC HMI Comfort Outdoor Panels 7" & 15" : All versions < V15 Update 4 ; affected SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F : All versions < V15 Update 4 ; affected SIMATIC WinCC Runtime Advanced : All versions < V15 Update 4 ; affected SIMATIC WinCC Runtime Professional : All versions < V15 Update 4 ; affected SIMATIC WinCC (TIA Portal) : All versions < V15 Update 4

Sources

SourceLicence
CVE List (CVEProject cvelistV5)CVE Program Terms of Use
EPSS (FIRST.org)FIRST — attribution requested
ENISA EUVDENISA — reproduction authorised, source acknowledged
CERT-FR (ANSSI)Licence Ouverte / Etalab 2.0
NVD (NIST) via fkie-cad/nvd-json-data-feedsPublic domain — this product uses data from the NVD API but is not endorsed or certified by the NVD